Single Splits – RAC Ceiling Concealed / SRR35ZM-S / SRC35ZMX-S

Category:

Description

SRR35ZM-S

Ceiling Concealed – Indoor Unit

SRR35ZM-S / SRC35ZMX-S

Ceiling concelaed RAC indoor unit with a nominal cooling capapcity of 2.5 kW.

Technical Specifications


Data Sheet (Printer Friendly)

 

General Data
Nominal cooling capacity (min-max) kW 3.5 (1.0 – 3.9)
Nominal heating capacity (min-max) kW 4.2 (1.5 – 5.2)
Exterior Dimensions (H x W x D) mm Unit:200 x 750 x 500
Net Weight kg 20.5
Air Flow Cooling (Hi/Me/Lo) m3/min 10.0 / 8.5 / 7.0 / 5.0
Air Flow Heating (Hi/Me/Lo) m3/min 10.5 / 9.5 / 8.5 / 6.5
Sound Pressure Level Cooling (Hi/Me/Lo) dB(A) 38 / 34 / 31 / 25
Sound Pressure Level Heating (Hi/Me/Lo) dB(A) 41 / 38 / 35 /29


Schematics



Ceiling Concealed – Outdoor Unit

SRC35ZMX-S

RAC outdoor unit with a nominal cooling capacity of 3.5 kW.

Technical Specifications


 

 

General Data
Nominal cooling capacity (min-max) kW 3.5 (1.0 -3.9)
Nominal heating capacity (min-max) kW 4.2 (1.5 -5.2)
EER (Energy Label) 3.57
COP (Energy Label) 4.08
Exterior Dimensions (H x W x D) mm 595 x 780(+62) x 290
Net Weight kg 35
Sound Pressure Level (Cooling/Heating) dB(A) 50/50
Energy class (Cooling/Heating) A++/A+
SEER “Average climate”/(Energy label) 6.31
SCOP “Average climate”/(Energy label) 4.02

 

 

Electrical Data
Pdesignc kW 3.50
Pdesignh (@-10°C) kW 3.55
Annual electricity consumption (Cooling/Heating) kWh/a 195 / 1238
Power Source 1Phase, 220 – 240V, 50Hz
Inrush current (220/230/240v) A 5.0 / 4.8 / 4.6
Max. running current A 8
Power consumption (Cooling/Heating) kW 0.98 / 1.03

 

Installation
Refrigerant (GWP) R410A (2088)
Designated heating season Average
Ref. Piping Size (Liquid/Gas) Ø mm 6.35 (1/4″) / 9.52 (3/8″)
Ref. Max Piping Length m Max. 15
Vertical Height differences / Outdoor is higher/lower m Max. 10 / Max. 10

Schematics