Description

Heat Recovery – Outdoor Unit

FDCH960KXE6

Heat Pump – Outdoor Unit

VRF outdoor unit with a nominal cooling capacity of 101.0 kW.

Technical Specifications


Data Sheet (Printer Friendly)

 

General Data
Indoor Unit Combination kW 450KXE6 + 504KXE6
Nominal cooling capacity kW 96
Nominal heating capacity kW 108
Exterior Dimensions (H x W x D) mm 2048 x 2700 x 720
Net Weight kg 336+358
Number of connectable indoor units - 69
Capacity connection - 50-140

 

 

Electrical Data
Power Source - 3 Phase 380-415V, 50Hz
Power consumption Cooling kW 27.7
Power consumption Heating kW 28.22
Operating Current Cooling A 45.2-41.3
Operating Current Heating A 46.9-43.0
Installation
Piping Size - Liquid line Ø mm 19.05 (3/4")
Piping Size - Gas line Ø mm 38.1 (1 1/2") [34.92 (1 3/8")]