Description
Heat Recovery – Outdoor Unit
FDC735KXRE6
Heat Recovery – Outdoor Unit
VRF outdoor unit with a nominal cooling capacity of 73.5 kW.
Technical Specifications
Data Sheet (Printer Friendly)
| Indoor Unit Combination | kW | 335KXRE6-K + 400KXRE6 |
| Nominal cooling capacity | kW | 73.5 |
| Nominal heating capacity | kW | 82.5 |
| Exterior Dimensions (H x W x D) | mm | (1690 x 1350 x 720) x 2 |
| Net Weight | kg | 337x2 |
| Number of connectable indoor units | - | 53 |
| Capacity connection | - | 50-160 |
| Power Source | - | 3 Phase 380-415V, 50Hz |
| Power consumption Cooling | kW | 21.08 |
| Power consumption Heating | kW | 21.3 |
| Operating Current Cooling | A | 34.4- 31.5 |
| Operating Current Heating | A | 35.4- 32.4 |
| Piping Size - Liquid line | Ø mm | 15.88 (5/8") |
| Piping Size - Suction Gas line | Ø mm | 31.75 (1 1/4") [34.92 (1 3/8")] |
| Piping Size - Discharge Gas line | Ø mm | 25.4 (1")[28.58(1 1/8")] |