Description
Heat Recovery – Outdoor Unit
FDC335KXRE6
VRF outdoor unit with a nominal cooling capacity of 33.5 kW.
Technical Specifications
Data Sheet (Printer Friendly)
Nominal cooling capacity | kW | 33.5 |
Nominal heating capacity | kW | 37.5 |
Exterior Dimensions (H x W x D) | mm | 1690 x 1350 x 720 |
Net Weight | kg | 256 |
Sound Pressure Level (Cooling/Heating) | dB(A) | 62/63 |
Number of connectable indoor units | - | 30 |
Capacity connection | - | 50-200 |
Power Source | - | 3 Phase 380-415V, 50Hz |
Power consumption Cooling | kW | 9.98 |
Power consumption Heating | kW | 9.55 |
Operating Current Cooling | A | 15.9- 14.8 |
Operating Current Heating | A | 15.5-14.2 |
Piping Size - Liquid line | Ø mm | 12.7 (1/2") |
Piping Size - Suction Gas line | Ø mm | 25.4 (1") [22.22 (7/8")] |
Piping Size - Discharge Gas line | Ø mm | 19.05 (3/4") |