Description
Heat Recovery – Outdoor Unit
FDC1235KXRE6
Heat Recovery – Outdoor Unit
VRF outdoor unit with a nominal cooling capacity of 123.5 kW.
Technical Specifications
Data Sheet (Printer Friendly)
Indoor Unit Combination | kW | 615KXRE6 + 615KXRE6 |
Nominal cooling capacity | kW | 123.5 |
Nominal heating capacity | kW | 138 |
Exterior Dimensions (H x W x D) | mm | (2048 x 1350 x 720) x 2 |
Net Weight | kg | 375x2 |
Number of connectable indoor units | - | 72 |
Capacity connection | - | 50-130 |
Power Source | - | 3 Phase 380-415V, 50Hz |
Power consumption Cooling | kW | 42.94 |
Power consumption Heating | kW | 38.22 |
Operating Current Cooling | A | 69.4- 63.6 |
Operating Current Heating | A |
Piping Size - Liquid line | Ø mm | 19.05 (3/4") |
Piping Size - Suction Gas line | Ø mm | 38.1 (1 1/2") [34.92 (1 3/8")] |
Piping Size - Discharge Gas line | Ø mm | 28.58 (1 1/8") |