Single Splits – PAC Ceiling Cassette / FDT60ZMXVF

Category:

Description

FDT60VF

Ceiling Cassette – Indoor Unit

FDT60ZMXVF

Ceiling cassette PAC indoor unit with a nominal cooling capacity of 6.0 kW.a

Technical Specifications


 

General Data
Nominal cooling capacity (min-max) kW 5.6 (1.1 – 6.3)
Nominal heating capacity (min-max) kW 6.7 (0.6 – 7.1)
Exterior Dimensions (H x W x D) mm Unit: 246 x 840 x 840; Panel: 35 x 950 x 950
Net Weight kg 29.5 (Unit: 24; Panel: 5.5)
Air Flow Cooling (Hi/Me/Lo) m3/min 28/ 18 / 16 / 14
Air Flow Heating (Hi/Me/Lo) m3/min 28/ 18 / 16 / 14
Sound Pressure Level Cooling (Hi/Me/Lo) dB(A) 46/ 33 / 31 / 30
Sound Pressure Level Heating (Hi/Me/Lo) dB(A) 46/ 33 / 31 / 30

 

Schematics



Ceiling cassette – Outdoor Unit

SRC60ZMX-S

PAC outdoor unit with a nominal cooling capacity of 6.0 kW.

Technical Specifications


 

 

General Data
Nominal cooling capacity (min-max) kW 5.6 (1.1 – 6.3)
Nominal heating capacity (min-max) kW 6.7 (0.6 – 7.1)
EER (Energy Label) 3.68
COP (Energy Label) 3.94
Exterior Dimensions (H x W x D) mm 640 x 800 (+71) x 290
Net Weight kg 45
Sound Pressure Level (Cooling/Heating) dB(A) 54/54
Energy class (Cooling/Heating) A++/A
SEER “Average climate”/(Energy label) 7.69
SCOP “Average climate”/(Energy label) 3.86

 

 

Electrical Data
Pdesignc kW 5.6
Pdesignh (@-10°C) kW 5.9
Annual electricity consumption (Cooling/Heating) kWh/a 255 / 2139
Power Source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz
Inrush current (220/230/240v) A 5
Max. running current A 15
Power consumption (Cooling/Heating) kW 1.52 / 1.70

 

Installation
Refrigerant (GWP) R410A (2088)
Designated heating season Average
Ref. Piping Size (Liquid/Gas) Ø mm 6.35 (1/4″) / 12.7 (1/2″)
Ref. Max Piping Length m Max. 30
Vertical Height differences / Outdoor is higher/lower m Max. 20 / Max. 20

Schematics