Multi Splits – PAC Compact Ceiling Cassette/ FDTC125VSPVF

Description

FDTC60VF x2

Compact Ceiling Cassette – Indoor Unit

FDTC125VSPVF

Ceiling cassette PAC indoor unit with a nominal cooling capacity of 6.0 kW.

Technical Specifications


Data Sheet (Printer Friendly)

 

General Data
Nominal cooling capacity (min-max) kW 12.5 (5.0 – 14.0)
Nominal heating capacity (min-max) kW 14.0 (4.0 – 16.0)
Exterior Dimensions (H x W x D) mm Unit: 248 x 570 x 570; Panel: 35 x 700 x 700
Net Weight kg 18.5 (Unit: 15; Panel: 3.5)
Air Flow Cooling (Hi/Me/Lo) m3/min 13.5/ 13.5 / 10 / 7
Air Flow Heating (Hi/Me/Lo) m3/min 13. 5/ 13.5 / 10 / 8
Sound Pressure Level Cooling (Hi/Me/Lo) dB(A) 47 / 46 / 39 / 30
Sound Pressure Level Heating (Hi/Me/Lo) dB(A) 47 / 46 / 39 / 32

 

Schematics



Compact Ceiling cassette – Outdoor Unit

FDC125VS

PAC outdoor unit with a nominal cooling capacity of 12.5 kW.

Technical Specifications


 

 

General Data
Nominal cooling capacity (min-max) kW 12.5 (5.0 – 14.0)
Nominal heating capacity (min-max) kW 14.0 (4.0 – 16.0)
EER (Energy Label) 2.34
COP (Energy Label) 3.03
Exterior Dimensions (H x W x D) mm 845 x 970 x 370
Net Weight kg 83
Sound Pressure Level (Cooling/Heating) dB(A) 50/51

 

 

Electrical Data
Power Source 3 Phase 380-415V 50Hz, 3 Phase 380V 60Hz
Inrush current (220/230/240v) A 5
Max. running current A 15
Power consumption (Cooling/Heating) kW 5.35 / 4.62

 

Installation
Ref. Piping Size (Liquid/Gas) Ø mm 9.52 (3/8″) / 15.88 (5/8″)
Ref. Max Piping Length m Max. 50
Vertical Height differences / Outdoor is higher/lower m Max. 30 / Max. 15

Schematics