Multi Splits – PAC Ceiling Suspended/ FDE100VNXPVG

Category:

Description

FDE50VG x2

Ceiling Suspended – Indoor Unit

FDE100VNXPVG

Ceiling suspended PAC indoor unit with a nominal cooling capacity of 5.0 kW.

Technical Specifications


Data Sheet (Printer Friendly)

 

General Data
Nominal cooling capacity (min-max) kW 10.0 (4.0 – 11.2)
Nominal heating capacity (min-max) kW 11.2 (4.0 – 12.5)
Exterior Dimensions (H x W x D) mm Unit:210 x 1070 x 690
Net Weight kg 28
Air Flow Cooling (Hi/Me/Lo) m3/min 13/ 10 / 9 / 7
Air Flow Heating (Hi/Me/Lo) m3/min 13/ 10 / 9 / 7
Sound Pressure Level Cooling (Hi/Me/Lo) dB(A) 46/ 38/ 36/ 31
Sound Pressure Level Heating (Hi/Me/Lo) dB(A) 46/ 38/ 36/ 31

 

Schematics




Ceiling Suspended – Outdoor Unit

FDC100VNX

PAC outdoor unit with a nominal cooling capacity of 10.0 kW.

Technical Specifications


 

 

General Data
Nominal cooling capacity (min-max) kW 10.0 (4.0 – 11.2)
Nominal heating capacity (min-max) kW 11.2 (4.0 – 12.5)
EER (Energy Label) 3.33
COP (Energy Label) 3.30
Exterior Dimensions (H x W x D) mm 1300 x 970 x 370
Net Weight kg 105
Sound Pressure Level (Cooling/Heating) dB(A) 48 / 50
Energy class (Cooling/Heating) A/A
SEER “Average climate”/(Energy label) 5.53
SCOP “Average climate”/(Energy label) 3.94

 

 

Electrical Data
Pdesignc kW 10
Pdesignh (@-10°C) kW 10.8
Annual electricity consumption (Cooling/Heating) kWh/a 634/3836
Power Source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz
Inrush current (220/230/240v) A 5
Max. running current A 24
Power consumption (Cooling/Heating) kW 3.00 / 3.39

 

Installation
Refrigerant (GWP) R410A (2088)
Designated heating season Average
Ref. Piping Size (Liquid/Gas) Ø mm 9.52 (3/8″) / 15.88 (5/8″)
Ref. Max Piping Length m Max. 100
Vertical Height differences / Outdoor is higher/lower m Max. 30 / Max. 15

Schematics