VRF (KX) – Outdoor/ Heat Recovery / FDC450KXRE6

Açıklama

Heat Recovery – Outdoor Unit

FDC450KXRE6

VRF outdoor unit with a nominal cooling capacity of 45.0 kW.

Technical Specifications


Data Sheet (Printer Friendly)

 

General Data
Nominal cooling capacity kW 45
Nominal heating capacity kW 50
Exterior Dimensions (H x W x D) mm 1690 x 1350 x 720
Net Weight kg 337
Sound Pressure Level (Cooling/Heating) dB(A) 62.5/62.5
Number of connectable indoor units - 40
Capacity connection - 50-200
Electrical Data
Power Source - 3 Phase 380-415V, 50Hz
Power consumption Cooling kW 13.49
Power consumption Heating kW 13.32
Operating Current Cooling A 21.6- 19.8
Operating Current Heating A 22.0- 20.1
Installation
Piping Size - Liquid line Ø mm 12.7 (1/2")
Piping Size - Suction Gas line Ø mm 25.4 (1") [28.58 (1 1/8")]
Piping Size - Discharge Gas line Ø mm 25.4 (1") [22.22 (7/8")]