VRF outdoor unit with a nominal cooling capacity of 45.0 kW.
Technical Specifications
Data Sheet (Printer Friendly)
| Nominal cooling capacity | kW | 45 |
| Nominal heating capacity | kW | 50 |
| Exterior Dimensions (H x W x D) | mm | 1690 x 1350 x 720 |
| Net Weight | kg | 337 |
| Sound Pressure Level (Cooling/Heating) | dB(A) | 62.5/62.5 |
| Number of connectable indoor units | - | 40 |
| Capacity connection | - | 50-200 |
| Power Source | - | 3 Phase 380-415V, 50Hz |
| Power consumption Cooling | kW | 13.49 |
| Power consumption Heating | kW | 13.32 |
| Operating Current Cooling | A | 21.6- 19.8 |
| Operating Current Heating | A | 22.0- 20.1 |
| Piping Size - Liquid line | Ø mm | 12.7 (1/2") |
| Piping Size - Suction Gas line | Ø mm | 25.4 (1") [28.58 (1 1/8")] |
| Piping Size - Discharge Gas line | Ø mm | 25.4 (1") [22.22 (7/8")] |