Açıklama
Heat Recovery – Outdoor Unit
FDC335KXRE6
VRF outdoor unit with a nominal cooling capacity of 33.5 kW.
Technical Specifications
Data Sheet (Printer Friendly)
| Nominal cooling capacity | kW | 33.5 |
| Nominal heating capacity | kW | 37.5 |
| Exterior Dimensions (H x W x D) | mm | 1690 x 1350 x 720 |
| Net Weight | kg | 256 |
| Sound Pressure Level (Cooling/Heating) | dB(A) | 62/63 |
| Number of connectable indoor units | - | 30 |
| Capacity connection | - | 50-200 |
| Power Source | - | 3 Phase 380-415V, 50Hz |
| Power consumption Cooling | kW | 9.98 |
| Power consumption Heating | kW | 9.55 |
| Operating Current Cooling | A | 15.9- 14.8 |
| Operating Current Heating | A | 15.5-14.2 |
| Piping Size - Liquid line | Ø mm | 12.7 (1/2") |
| Piping Size - Suction Gas line | Ø mm | 25.4 (1") [22.22 (7/8")] |
| Piping Size - Discharge Gas line | Ø mm | 19.05 (3/4") |