Single Splits – RAC Wall Mounted / SRK35ZMX-S / SRC35ZMX-S

Category:

Description

SRK35ZMX-S

Wall Mounted – Indoor Unit

SRK35ZMX-S / SRC35ZMX-S

Wall-mounted RAC indoor unit with a nominal cooling capacity of 3.5 kW.

Technical Specifications


Data Sheet (Printer Friendly)

 

General Data
Nominal cooling capacity (min-max) kW 3.5 (0.9~4.1)
Nominal heating capacity (min-max) kW 4.3 (0.9~5.1)
Exterior Dimensions (H x W x D) mm Unit:309 x 890 x 220
Net Weight kg 13.5
Air Flow Cooling (Hi/Me/Lo) m3/min 13.5 / 9.5 / 6.5 / 5.0
Air Flow Heating (Hi/Me/Lo) m3/min 14.0 / 11.0 / 8.0 / 6.5
Sound Pressure Level Cooling (Hi/Me/Lo) dB(A) 43 / 33 / 25 / 22
Sound Pressure Level Heating (Hi/Me/Lo) dB(A) 42 / 35 / 27 / 22


Schematics



Wall Mounted – Outdoor Unit

SRC35ZMX-S
RAC outdoor unit with a nominal cooling capacity of 3.5 kW.

Technical Specifications


 

 

General Data
Nominal cooling capacity (min-max) kW 3.5 (0.9~4.1)
Nominal heating capacity (min-max) kW 4.3 (0.9~5.1)
EER (Energy Label) 4.14
COP (Energy Label) 4.48
Exterior Dimensions (H x W x D) mm 595 x 780(+62) x 290
Net Weight kg 35
Sound Pressure Level (Cooling/Heating) dB(A) 50/50
Energy class (Cooling/Heating) A++/A+
SEER “Average climate”/(Energy label) 7.20
SCOP “Average climate”/(Energy label) 4.27

 

 

Electrical Data
Pdesignc kW 3.50
Pdesignh (@-10°C) kW 3.30
Annual electricity consumption (Cooling/Heating) kWh/a 171/1082
Power Source 1Phase, 220 – 240V, 50Hz
Inrush current (220/230/240v) A 4.6 / 4.4 / 4.2
Max. running current A 8
Power consumption (Cooling/Heating) kW 0.845 / 0.96

 

Installation
Refrigerant (GWP) R410A (2088)
Designated heating season Average
Ref. Piping Size (Liquid/Gas) Ø mm 6.35 (1/4″) / 9.52 (3/8″)
Ref. Max Piping Length m Max. 15
Vertical Height differences / Outdoor is higher/lower m Max. 10 / Max. 10

Schematics